The UNI-T UT523A is a professional earth resistance and soil resistivity tester for grounding-system commissioning and maintenance — measuring earth (ground) resistance up to 210 kΩ, soil resistivity by the 4-pole Wenner method, and earth voltage up to AC 750 V.
It uses a rated-current pole-changing method (max 20 mA) with automatic AFC test frequencies (128/111/105/94 Hz) to reject interference, auto-ranges across all scales, and holds ±(2%+5) accuracy — ideal for substations, lightning-protection systems, towers and electrical installations. Genuine UNI-T product supplied by Digilog.pk with warranty and English manual.
Key Features
- 🌍 Earth resistance 0.00 Ω ~ 210 kΩ at ±(2%+5), auto-range
- 🪨 Soil resistivity (ρ) by 4-pole Wenner method, up to 9000 kΩ·m
- ⚡ Earth voltage AC 0 ~ 750 V measurement
- 📡 AFC test frequencies (128/111/105/94 Hz) reject stray interference
- 🔧 Rated-current pole-changing method, max 20 mA test current
- 🛡️ Short-circuit current ≤30 mA, open-circuit ≤40 V; auto power-off
Technical Specifications
| Earth resistance range | 0.00 Ω ~ 210 kΩ (5 ranges) |
|---|---|
| Earth resistance accuracy | ±(2% + 5) |
| Soil resistivity range | 0 Ω·m ~ 9000 kΩ·m (ρ = 2πaR, Wenner method) |
| Earth voltage | AC 0.00 ~ 750 V, ±(2% + 5) |
| Test frequencies | 128 / 111 / 105 / 94 Hz (AFC) |
| Measuring current (earth R) | Rated-current pole-changing, max 20 mA |
| Short-circuit test current | AC 30 mA max |
| Open-circuit test voltage | AC 40 V max |
| Auto range | Yes |
What's in the Box
- UT523A earth / soil resistivity tester
- Test lead set
- Auxiliary earth spikes
- Carrying case
- Batteries
- English user manual
Downloads
Certifications: CE | HS Code: 9030.39